Specialized Container House
Background Introduction
In recent years, container houses, which were originally used for transporting heavy goods, have gradually been repurposed by architects for applications such as cafes and boutique hotels due to their advantages of low cost, high strength, durability, and recyclability, especially with the loosening of construction regulations. Internationally, container houses have long been used for hazardous chemical storage facilities and emergency shelters for personnel.
The need for hazardous chemical storage and emergency shelters for personnel has always been a crucial aspect in many industries. However, storing these chemicals or providing emergency shelters involves a series of safety risks, with fire and explosion being among the most common. To address these challenges, Liansuo Construction Technology has modified container houses, categorizing the products into fireproof, explosion-proof, flame-resistant, and personnel shelter types for hazardous chemical storage and emergency sheltering. These products ensure employee safety, prevent environmental pollution, and protect property from damage while adhering to safety and compliance standards for customers.
References to Domestic and International Standards
- CNS11227-1: Fire Resistance Test Method – Part 1: Door and Rolling Door Components
- CNS6532: Fire Resistance Test Method for Building Interior Materials
- CNS12514-8: Fire Resistance Test Method for Non-Load-Bearing Exterior Walls
- CNS12514-5: Fire Resistance Test Method for Floors and Roof Components
- CNS12514-1: Fire Resistance Test Method for Building Structural Components – Part 1
- CNS941: Steel Cable Load Testing
- Standards for the Establishment and Safety Management of Manufacturing and Storage Facilities for Hazardous Substances and Combustible High-Pressure Gases
- FM 1-44: Damage-Limiting Construction (Datasheet)
- FM6049: FM Approval Standard for Flammable Liquid Storage Buildings and Lockers
- FM4440: FM Approval Standard for Explosion Venting Systems Including Fasteners and Latches for Damage-Limiting Construction
- NFPA 30: Flammable and Combustible Liquids Code
LS-20GP01 Chemical Container House (Explosion-proof /Fireproof Type) Product Technical Specifications
No. | Part Name | Material | Technical Parameters |
---|---|---|---|
1 | Wall | Corrugated steel panel + stamped metal composite panel (thickness 9.5mm; electrostatic powder coating) + rock wool (128K) + ceramic wool (128K) + square steel tube (100x100x3mm) | Wall thickness: 140mm; Fire resistance: ≥3 hours (CNS12514-5); Explosion resistance: ≥4.8kPa (FM1-44) |
2 | Roof | Corrugated steel panel + reinforced cement fiberboard (9mm) + rock wool + square steel tube (100*100*3mm) | |
3 | Roof Explosion Vent | LS explosion vent Panel ; FM Approved vent fastener/LS-EV01 | damage force value: 700N; explosion vent pressure: 0.96kPa-1.92kPa |
4 | Floor | Stamped metal composite panel (electrostatic powder coating) | Flame resistance: Class 1 (CNS6532) |
5 | Frame | Galvanized steel pipe + electrostatic powder coating | Structural strength meets FM6049 requirements |
6 | Fireproof and Explosion-proof Door | Steel (Width: 2114mm * Height: 2231mm) | Fire resistance: ≥2 hours (CNS11227-1); Explosion resistance: ≥4.8kPa (FM1-44) |
7 | Foundation | Special fixed device | C30 concrete / thickness: 100-200mm |
8 | Dimensions | 20-foot container house | 6058 * 2438 * 2591mm |
LS-20GP03 Personnel Shelter (Explosion-resistant Type) Product Technical Specifications
No. | Part Name | Material | Technical Parameters |
---|---|---|---|
1 | Roof/Wall | Corrugated steel panel + stamped metal composite panel (thickness 9.5mm; electrostatic powder coating) + rock wool (128K) + ceramic wool (128K) + square steel tube (100*100*3mm) | Wall thickness: 140mm; Fire resistance: ≥3 hours (CNS12514-5); Explosion resistance: ≥4.8kPa (FM1-44) |
2 | Floor | Stamped metal composite panel (electrostatic powder coating) | Flame resistance: Class 1 (CNS6532) |
3 | Frame | Galvanized steel pipe + electrostatic powder coating | Structural strength meets FM6049 requirements |
4 | Fireproof and Explosion-proof Door | Steel (Width: 2114mm * Height: 2231mm) | Fire resistance: ≥2 hours (CNS11227-1) |
5 | Foundation | Special fixed device | C30 concrete / thickness: 100-200mm |
6 | Dimensions | 20-foot container house | 6058 * 2438 * 2591mm |